Description, Figure 2 trusted, Fibre tx/rx unit block diagram – Rockwell Automation T8314 Trusted Fibre TR/TX Unit User Manual

Page 7: Trusted, Fibre tx rx unit t8314

Advertising
background image

Trusted

TM

Fibre TX RX Unit T8314

Issue 10 Sep 08

PD-T8314

7

1. Description

The Trusted

TM

Fibre TX/RX Unit T8314 is designed to be DIN rail mounted in the rear area of a

cabinet/bay containing the Trusted

TM

Controller Chassis T8100. A block diagram of the Unit is shown

in Figure 2 below:

Figure 2 Trusted

TM

Fibre TX/RX Unit Block Diagram

The Unit provides a communications connection interface between the Trusted

TM

Controller Chassis

and a remote Expander Chassis.

The Positive Emitter Coupled Logic (PECL) signal from the Trusted

TM

Expander Interface Module in

the Controller Chassis is connected to the Unit by a Trusted

TM

Expander Cable TC-302. The signal is

fed through an isolator, then filtered and terminated before being connected to the PECL input of the
fibre-optic transceiver. The fibre-optic signal is transmitted to a similar Unit at the remote end via a
Single Mode Fibre-Optic Cable. The fibre-optic transceiver at the remote end of the link converts the
signal back to a PECL signal before transmitting it to the Trusted

TM

Expander Processor Module via a

filter/termination circuit, isolator and ‘F’ filter. Signals originating from the Trusted

TM

Expander

Processor Module in the remote Expander Chassis are processed in the same manner.

Advertising