17. With the circuit breaker kit now completely installed,
drive operation should be checked. Close the cabiĆ
net door. Reapply power to the incoming line feedĆ
ing the controller and close the incoming circuit
breaker. Start the drive. A failure to start indicates
the possibility that plant power wiring was reconĆ
nected with improper phase rotation. To correct this
problem, once again remove power from the plant
line feeding the drive, reverse any two of the three
incoming leads into the line side terminations of the
circuit breaker, and once again apply plant power.
The drive should now start. If it does not, refer to
section 5 of l/M DĆ3851.
REPAIR PARTS
A complete parts list is provided on assembly drawĆ
ing 705390Ć3.