Rockwell Automation MAI32AD 32-Analogue Input Module Differential Input User Manual
Page 3

MAI32*AD October 2005 – Issue 4
3
Triguard SC300E MAI32*AD 32-Channel A/I Module Differential Input
SPECIFICATION
Input parameters
All models have 32 input channels configured as follows:
Model number
Voltage input applications
MAI32LAD
0 to 5Vdc
MAI32MAD
0 to 10Vdc
Current input applications
0 to 20mA. Use TAI16AIR (BIR) with MAI32LAD
0 to 40mA Use TAI16AIR (BIR) with MAI32MAD
Model
See under “input range”
Channels
32
Architecture
TMR
Indicators
Health 3 x On Line
Channel Input Test Ponts
Switch selectable on front panel
Input range
MAI32LAD: 0 to 5Vdc
MAI32MAD: 0 to 10Vdc
Input overrange protection
±40Vdc
Resolution
12 bits
Accurancy @ 25°C
± 0.04% over full signal range
Stability (temperature coefficient)
±20ppm/°C
Analogue to digital converter
SAR (monotonic)
Sample rate
40ms nominal
Input impedance
>20M ohm
Power off impedance
>12k ohm
Common mode range
±11Vdc
Isolation
1kVdc system/channel
±15Vdc channel to channel
Power consumption
By system
By input loads
7.5W excluding input loads
3.2W maximum for 20mA module
Overall size (mm)
Overall size (inches)
400(9U)H x 397L x 28W
15.75H x 15.63L x 1.1W
Weight
1.6kg