SDS-8830
Trusted

TM

Industrial Control System

Trusted

TM

40 Channel Analogue Input FTA -T8830

ICS Triplex

Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-

www.icstriplex.com

BLOCK DIAGRAM

(SmartSlot Link Connector is unused)

Figure 2

ELECTRICAL SPECIFICATION

Number of Field Inputs

40

Internal Use Inputs

2

Type of Input Terminals

MKKDS 3

Type of Power Terminals

MVSTBR 2.5

Acceptable Wire Sizes

UL

CSA

30-12 AWG 15A 300V
28-12 AWG 10A 300V

DIN Rail Compatibility

EN 50022

NS 35/7.5

NS 35/15

NS 32

Testing

100% electrical (continuity and
short-circuit)

Intrinsic Safety

External barrier

Dropping Resistor

250D, 0.5W

MECHANICAL
SPECIFICATION


Dimensions (HxWxD):
335mm x 111mm x 51mm
(13.2ins x 4.4ins x 2ins)

Weight:
0.9kg (2.0lbs)

ENVIRONMENTAL

Operating Temperature:
-5

°C to 60°C

(23

°F to 140°F)


Storage Temperature
-25

°C to 70°C

(-13

°F to 158°F)

Operating Humidity:
10 to 95%, non-condensing

Vibration:
9 to 150Hz

1g


Shock:
15g, ½ sine wave, 11ms

EMI:
ESD
Air discharge to 8kV
Contact discharge to 4kV
Conducted
10V/m, 150kHz to 80MHz
Radiated Fields
10V/m, 80Mhz to 1GHz
Transients and Bursts
2kV, 2.5kHz for t=60 seconds