Table 14 specific diagnostic error codes, Trusted, Module t8442 – Rockwell Automation T8442 Trusted TMR Speed Monitor User Manual
Page 45

Trusted
TM
Module T8442
Issue 8 Apr 10
PD-T8442
45
0x6Cmn
Qd
0-3
Op
0-5
SFIU_RELAY_DRIVE_XTALK_FAUL
T
Crosstalk between relay commands, or DIAGs
0x6Cmn
4+
(Qd
0-3)
Op
0-5
SFIU_RELAY_IMON_XTALK_FAULT
Crosstalk between relay IMONs
0x6D0n
Op
0-5
SFIU_IMON_QUAD_DISCREP
(LEG1)
IMON Leg1 Q1-Q2 Discrepancy
0x6D1n
Op
0-5
SFIU_IMON_QUAD_DISCREP
(LEG2)
IMON Leg2 Q1-Q2 Discrepancy
0x6D3n
Op
0-5
SFIU_RLY_IMON_LEG_DISCREP
IMON Leg to Leg Imbalance
0x6E0n
Gp
0-2
SFIU_VMON_QUAD_DISCREP
(24V1)
24V1 Q1-Q2 Discrepancy
0x6E1n
Gp
0-2
SFIU_VMON_QUAD_DISCREP
(24V2)
24V2 Q1-Q2 Discrepancy
0x6E2n
Gp
0-2
SFIU_VMON_QUAD_DISCREP
(15V1)
15V1 Q1-Q2 Discrepancy
0x6E3n
Gp
0-2
SFIU_VMON_QUAD_DISCREP
(15V1)
15V2 Q1-Q2 Discrepancy
0x6F0n
Gp
0-2
SFIU_CONTACT_QUAD_DISCREP
Relay Contact Q1-Q2 Discrepancy
Table 14 Specific Diagnostic Error Codes