SDS-8841
Trusted

TM

Industrial Control System

Trusted

TM

8 Channel RTD FTA -T8841

ICS Triplex

Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-

www.icstriplex.com

BLOCK DIAGRAM

ELECTRICAL SPECIFICATION

Number of Inputs

8 Channels (2 or 3-wire)

Voltage Range

20 to 32V dc

Power Isolation

±250V dc

Power Consumption (per channel @ 24V
dc)

60 to 720mW

Sensor Excitation Current

0.8mA

Current Output (normal operating range)

4 to 20mA

MECHANICAL
SPECIFICATION


Dimensions (HxWxD):
110mm x 145mm x 68mm
(4.3ins x 5.7ins x 2.6ins)

Weight:
248gms
(0.55lbs)

ENVIRONMENTAL


Operating Temperature:

-5

°C to 60°C

(23

°F to 140°F)


Operating Humidity:
5 to 95%, non-
condensing

Vibration:
10 to 57Hz

±0.075mm

57 to 150Hz 1.0g

Shock:
15g, ½ sine wave, 11ms

EMI (IEC 801):
ESD
Air discharge to 15kV
Contact discharge to 8kV

Radiated Fields
10V/m, 27MHz to
500MHz

Transients and Bursts
2kV, 2.5kHz for
t=60 seconds

Advertising