Trusted

TM

AN-T80008 MCB Discrimination

Issue 2 Feb 07

AN-T80008

5

Conclusion

The internal self-protection of T824x power units may cause them to trip before the MCBs. Ensure that
MCBs and other circuit protection devices are rated to ensure that any one short will not overload the
supply. Low current ratings are therefore recommended, to ensure that the protection device trips first,
due to its time/current curve.