B. High-Pressure and Low-Pressure Switches

If either switch trips, or if the compressor overtemperature
switch activates, that refrigerant circuit will be automati-
cally locked out by the CLO. To reset, manually move the
thermostat setting.

C. Freeze Protection Thermostat (FPT)

An FPT is located on the top and bottom of the evaporator
coil. They detect frost build-up and turn off the compressor,
allowing the coil to clear. Once the frost has melted, the
compressor can be reenergized by resetting the compressor
lockout.

D. Evaporator Fan Motor Protection

A manual reset, calibrated trip, magnetic circuit breaker
protects against overcurrent. Do not bypass connections or
increase the size of the breaker to correct trouble. Determine
the cause and correct it before resetting the breaker.

E. Condenser-Fan Motor Protection

Each condenser-fan motor is internally protected against
overtemperature.

Fuses are also located in the control box and feed power to
the condenser fan motors. Always replace blown fuses with
the correct size fuse as indicated on the unit fuse label.

XIII. RELIEF DEVICES

All units have relief devices to protect against damage from
excessive pressures (i.e., fire). These devices protect the high
and low side.

XIV. CONTROL CIRCUIT, 24-V

Each control circuit is protected against overcurrent by a
3.2 amp circuit breaker. Breaker can be reset. If it trips,
determine cause of trouble before resetting. See Fig. 40-42
for wiring.

XV. REPLACEMENT PARTS

A complete list of replacement parts may be obtained from
any Bryant distributor upon request.

XVI. DIAGNOSTIC LEDs

The IGC control board has a LED for diagnostic purposes.
The IGC error codes are shown in Table 33.

Table 33 — IGC LED Indications

LEGEND

NOTES:

1. There is a 3-second pause between error code displays.
2. If more than one error code exists, all applicable error codes will be

displayed in numerical sequence.

3. Error codes on the IGC will be lost if power to the unit is

interrupted.

ERROR CODE

LED INDICATION

Normal Operation

On

Hardware Failure

Off

Fan On/Off Delay Modified

1 Flash

Limit Switch Fault

2 Flashes

Flame Sense Fault

3 Flashes

Five Consecutive Limit Switch Faults

4 Flashes

Ignition Lockout Fault

5 Flashes

Inducer Switch Fault

6 Flashes

Rollout Switch Fault

7 Flashes

Internal Control Fault

8 Flashes

Software Lockout

9 Flashes

IGC — Integrated Gas Unit Controller
LED — Light-Emitting Diode

SEE DETAIL “C”

Fig. 39 — Spark Gap Adjustment