Table 2 — Fan Motor and Drive Data — Vertical Supply/Return

LEGEND

581A

210

240

300

208/230

and 460 v

575 v

208/230

and 460 v

575 v

208/230

and 460 v

575 v

LOW RANGE

Motor Hp

3.7

3

5

5

7.5

7.5

Motor Nominal Rpm

1725

1725

1745

1745

1745

1745

Maximum Continuous Bhp

4.25

3.45

5.75

5.75

8.63

8.63

Maximum Continuous Watts

3698

3149

4900

4900

7267

7267

Motor Frame Size

56HZ

56HZ

S184T

184T

S213T

S213T

Motor Shaft Diameter (in.)

7

/

8

7

/

8

1

1

/

8

1

1

/

8

1

3

/

8

1

3

/

8

Fan Rpm Range

647-886

810-1072

949-1206

949-1206

941-1176

941-1176

Motor Pulley Min. Pitch Diameter (in.)

2.7

3.1

3.7

3.7

4.8

4.8

Motor Pulley Max. Pitch Diameter (in.)

3.7

4.1

4.7

4.7

6.0

6.0

Blower Pulley Pitch Diameter (in.)

7.2

6.6

6.8

6.8

8.9

8.9

Blower Pulley Shaft Diameter (in.)

1.1875

1.1875

1.1875

1.1875

1.1875

1.1875

Blower Pulley Type

Fixed

Fixed

Fixed

Fixed

Fixed

Fixed

Pulley Center Line Distance (in.)

11.293-13.544 11.286-14.475

9.81-13.055

9.81-13.055

9.025-12.179 9.025-12.179

Belt, Quantity...Type...Length (in.)

1...BX...38

1...BX...38

1...BX...38

1...BX...38

1...BX...42

1...BX...42

Speed Change Per Turn — Moveable Pulley (rpm)

48

52

51

51

47

47

Moveable Pulley Maximum Full Turns

6

6

6

6

6

6

Factory Speed Setting (rpm)

767

941

1078

1078

1059

1059

HIGH RANGE
Motor Hp

5

5

7.5

7.5

10

10

Motor Nominal Rpm

1745

1745

1745

1745

1745

1745

Maximum Continuous Bhp

5.75

5.75

8.63

8.63

11.5

11.5

Maximum Continuous Watts

4900

4900

7267

7267

9582

9582

Motor Frame Size

S184T

184T

S213T

S213T

S215T

S215T

Motor Shaft Diameter (in.)

1

1

/

8

1

1

/

8

1

3

/

8

1

3

/

8

1

3

/

8

1

3

/

8

Fan Rpm Range

897-1139

873-1108

941-1176

941-1176

1014-1297

1014-1297

Motor Pulley Min. Pitch Diameter (in.)

3.7

3.7

4.8

4.8

4.3

4.3

Motor Pulley Max. Pitch Diameter (in.)

4.7

4.7

6.0

6.0

5.5

5.5

Blower Pulley Pitch Diameter (in.)

7.2

7.4

8.9

8.9

7.4

7.4

Blower Pulley Shaft Diameter (in.)

1.1875

1.1875

1.1875

1.1875

1.1875

1.1875

Blower Pulley Type

Fixed

Fixed

Fixed

Fixed

Fixed

Fixed

Pulley Center Line Distance (in.)

9.81-13.055

9.81-13.055

9.025-12.179 9.025-12.179 9.025- 2.179 9.025-12.179

Belt, Quantity...Type...Length (in.)

1...BX...38

1...BX...38

1...BX...42

1...BX...42

2...BX...38

2...BX...38

Speed Change per Turn — Moveable Pulley (rpm)

48

47

47

47

57

57

Moveable Pulley Maximum Full Turns

6

6

6

6

6

6

Factory Speed Setting (rpm)

1018

991

1059

1059

1156

1156

Bhp — Brake Horsepower