Watts F1113-6RFP User Manual

Flood protection shut down valve (4, Lassic, Eries

Advertising
background image

01/10

C

lassiC

s

eries

12541 Gulf Freeway

Houston, Texas 77034

(Ph) 713.943.0688

(Fx) 713.944.9445

www.watts.com

5

X

2

4

1

3

CLOSES VALVE

OPENS VALVE

FLOW

X

X

FC

To Floor

Drain

L

6

7

To Atmosphere

8

9

JB113

FS99

F113-6RFP (Globe)

F1113-6RFP (Angle)

FLOOD PROTECTION SHUT DOWN VALVE

(4”

and

larger

)

1 - Main Valve (Single Chamber)

2 - Model 22-1 Accelerator Control

3 - 3-Way Solenoid

Port 1 - Accelerator Cover

Port 2 - Atmosphere

Port 3 - Pressure

4 - Adjustable Closing Speed

5 - Adjustable Opening Speed

6 - Pressure Gauge

7 - Manual Reset Ball Valve

8 - JB113 Junction Box

9 - FS99 Flow Sensor

L - Limit Switch

X - Isolation Cocks

FC - Flo-Clean Strainer

Standard Components

Operations

The Watts Flood Protection Shutdown Valve system

prevents catastrophic property damage that can occur

due to Relief Valve discharge and/or a blocked or over-

whelmed floor drain during normal relief valve operation.

Typical conditions which can cause continuous relief

valve discharge are:

Fouled First Check Seat due to dirt, debris or rocks

Failed First Check Spring

Clogged or blocked Relief Valve Sensing Line

Relief Valve Diaphragm failure

The Watts 113-6RFP Flood Protection Shutdown Valve

is a normally open valve designed to be installed up-

stream of a Reduced Pressure Zone (RPZ) Backflow

Prevention device. It is normally open and closes drip-

tight when continuous relief valve discharge through the

drain pipe is sensed by the FS99 Flow Sensor, energiz-

ing the Solenoid Pilot. The Solenoid Pilot is equipped with

a Manual Operator which simulates power when manu-

ally engaged. The valve mounted JB113 Junction Box

is equipped with an adjustable time delay to avoid valve

closure due to intermittent or nuisance relief valve dis-

charge. The Limit Switch provides local visual and remote

electrical indication of valve closure. The valve remains

closed and cannot re-open if flow stops or electrical ser-

vice is interrupted, and must be manually reset after the

RPZ is diagnosed and/or repaired.

The valve comes complete with the valve mounted JB113

Junction Box with adjustable time delay, pre-wired So-

lenoid Valve, Manual Reset with Pressure Gauge, Limit

Switch and FS99 Flow Sensor (field installed). Fail-safe

operation is assured by closing valve upon Main Valve or

Pilot Diaphragm failure and a specially coated Main Valve

Stem for added protection.

• Installed upstream of Reduced Pressure Zone Backflow

Preventer.

• Normally Open Valve - Closes when discharge from

RPZ Relief Valve is sensed or by engaging Solenoid

Manual Operator.

• Limit Switch provides local visual and remote electrical

indication of valve closure.

• Valve must be manually reset. Pressure gauge

(provided) indicates valve reset for automatic service.

• Anti-Scale Coated Main Valve Stem for added

protection.

• Fail Safe operation - Valve closes upon Main Valve or

Pilot Diaphragm failure.

Advertising
This manual is related to the following products: