Installation, Maintenance, & Repair

Series 709/LF709/709DCDA

Double Check Valve Assemblies

Double Check Detector Assemblies

Sizes:

3

4

" – 10" (20-250mm)

RP/IS-709/709DCDA

8" (200mm) 709 OS&Y shown

Testing

For field testing procedure, reference IS-TK-DL, IS-TK-7,

IS-TK-9A, IS-TK-99E AND IS-TK-99D at www.watts.com
For other repair kits and service parts, reference PL-RP-BPD at

www.watts.com
For technical assistance, contact your local Watts

representative.

NOTICE

For Australia and New Zealand, line strainers should be in-

stalled between the upstream shutoff valve and the inlet of the

backflow preventer.

Its important that this device be tested periodically in compli-

ance with local codes, but at least once per year or more as

service conditions warrant. If installed on a fire sprinkler sys-

tem, all mechanical checks, such as alarm checks and back-

flow preventers, should be flow tested and inspected internally

in accordance with NFPA 13 and NFPA 25.

Installation Instructions

Watts Series 709 and LF709 Double Check Valve may be installed

in either a vertical or horizontal position.
Install valve inline with arrow on valve body pointing in the direction

of flow.
They should always be installed in an accessible location to facili-

tate testing and servicing.
Pipe lines should be thoroughly flushed to remove foreign material

before installing the unit. A strainer should be installed as shown,

ahead of backflow preventers to prevent discs from unnecessary

fouling.

CAUTION

!

Do not install with strainer when backflow preventer is used on

seldom-used water lines which are called upon during emergen-

cies, such as fire sprinkler lines, etc.
It is important that Series 709 and LF709 be tested periodically

in compliance with local codes, but at least once a year or more

often, depending upon system conditions. (Reference IS-TK-7 at

www.watts.com).

Clearance Required for Servicing

Size

DimenSion

A

in.

mm

in.

mm

2

1

2

" – 3

65-80

10

250

4

100

15

380

6

150

15

380

8

200

23

580

10

250

25

640

A

Local building or plumbing codes may require modifications to

the information provided. You are required to consult the local

building and plumbing codes prior to installation. If this informa-

tion is not consistent with local building or plumbing codes, the

local codes should be followed.
Need for Periodic Inspection/Maintenance: This product

must be tested periodically in compliance with local codes, but

at least once per year or more as service conditions warrant.

Corrosive water conditions, and/or unauthorized adjustments

or repair could render the product ineffective for the service in-

tended. Regular checking and cleaning of the product’s internal

components helps assure maximum life and proper product

function.

WARNING

!

Read this manual BeFoRe using this equipment.
Failure to read and follow all safety and use information

can result in death, serious personal injury, property

damage, or damage to the equipment.
Keep this manual for future reference.