Klimaire 13 SEER Series User Manual

Page 13

Advertising
background image

12

1/2

” bolt

5/16

” bolts

Fig. 9 COVER AND FAN

3.10 REMOVING THE TOP PANEL AND MOTOR

When motor requires changing follow the steps below:
Step 1: Go into electrical panel, disconnect motor power lines.

IMPORTANT NOTE

Disconnect main power to unit. Severe burns and electrical shock will occure if
you do not disconnect main power.

Step 2: Remove cover (be careful of motor wires)
Step 3: Be sure to place fan cover unit on the ground as indicated in Fig. 9

IMPROTANT NOTE
Do not place or lean fan blades on ground or against surface.

Step 4: Remove fan motor by removing 5/16

” bolts from cover.

Step 5: Remove fan blade from motor by removing 1/2

” bolt and place fan on the ground.

Step 6: Reverse removal process to reinstall the fan and motor.

IMPROTANT NOTE
When connecting motor wires be sure to check motor direction.

DESCRIPTION

1/4

” Χ 3/8” Hex Washer Head Concrete Screws

1/8

” Χ 1-1/2” Χ W (width of unit +4”) Metal straps

3/8

” Washers

QUANTITY

4
4
4

Step 4: Fasten (4) L-shaped stainless steel braces onto cabinet base using 1/4

” * 1/2”

Hex washer head stainless steel self tapping screws where indicated in detail

Fig.8.
IMPORTANT

Do not use screws longer than indicated 1/4

” * 2/3” and make sure that the brace

is attached on center of base ban where indicated in Fig.8

Damage will occrue to system.

Step 5: Drill 4 holes into cement base ensuring holes are 1//2

” dp.

Step 6: Assemble unit to cement pad using 1/4

” * 2” Hex washer head cement

screws make sure not to over tighten.

Step 7

:Finish unit assembly process as indicated in installation manual.

Step 1: Prior to installing clear pad of debris.
Step 2: Ensure cement pad is level.

IMPORTANT

Then cement pad must be made of HVAC-approved materials and must be the

proper thickness to accommodate fasteners.

Step 3: Center unit onto pad.

Damage will occur to condenser unit
if you remove fan bolts prior to cover removal.

NOTE: