The outdoor units are designed to be connected to a matching indoor coil with sweat
connect lines. Sweat connect units are factory charged with refrigerant for a match-
ing indoor coil plus 25 feet of field supplied lines.

Matching indoor coils are available with a thermostatic expansion valve or an orifice
for the most common usage. The orifice size and/or refrigerant charge may need to
be changed for some indoor-outdoor unit combinations, elevation differences or
total line lengths.

2.0 GENERAL

1.Limitations for the indoor unit, coil and appropriate accessories must also be observed.
2.The outdoor unit must not be installed with any duct work in the air stream. The outdoor fan is
the propeller type and is not designed to operate against any additional external static
pressure.
3.The maximum and minimum conditions for operation must be observed to assure a system
that will give maximum performance with minimum service.
4.This unit is not designed to operate with a low ambient kit. Do not modify the control system
to operate with any kind of Iow ambient kit.
5.The maximum allowable line length for this product is 150 feet

Just for Scroll compressor

.

1.2 LIMITATIONS

The unit should be installed in accordance with all National, State and Local Safety
Codes and the limitations listed below:

As soon as a unit is received, it should be inspected for possible damage during transit.
If damage is evident, the extent of the damage should be noted on the carrier's delivery
receipt. A separate request for inspection by the carrier's agent should be made in
writing. See Local distributor for more information.

1.1 INSPECTION

LIQUID
SERVICE VALVE

LIQUID-LINE FILTER-DRIER

Fig.1 Filter-Drier insatllation

4

Requirements For Installing/Servicing R410A Equipment

Gauge sets, hoses, refrigerant containers, and recovery system must be designed

to handle the POE or PVE type oils.
Manifold sets should be 800 PSIG high side and 250 PSIG low side with 550 PSIG
Iow side restart.
All hoses must have a 700 PSIG service pressure rating.
Leak detectors should be designed to detect refrigerant.
Recovery equipment (including refrigerant recovery containers) must be specifi-
cally designed to handle R410A.

Do not use an R-22 TXV.

A liquid-line filter drier is required on every unit. see the Fig.1

It will be more convenient to open
the Service valve after removing

the Underside Clapboard.

NOTE