2 condition monitoring and event display, 1 leds, Condition monitoring and event display – Richter SAFERUN User Manual

Page 10: Leds, Series mnk, mnk-b, Saferun, Pump condition monitoring system

Advertising
background image

Series MNK, MNK-B,

SAFERUN

®

Pump condition monitoring system

Page 10

9230-070-en

Revision 01

TM 7691

Edition 11/2009

6.2 Condition monitoring and

event display

Note:
see Section 1.4.

The monitoring mode is the normal mode of the
SAFERUN

®

. In this mode the following conditions can

be detected and displayed by the system:

Operation within the recommended operating
limits:

Direction of rotation:

Is determined every time the pump is put into op-
eration.

Qmin reached:

Basic setting: Q/Q

opt

= 8%

Qmin undershot:

The minimum flow rate Q

min

recommended by the

manufacturer is undershot; continuous operation in
this condition can result in damage to parts of the
pump.

Qmax reached:

Basic setting: Q/Q

opt

= 120%

Qmax exceeded:

The maximum value of the flow rate Q

max

recom-

mended by the manufacturer is exceeded; con-
tinuous operation in this condition can result in
damage to the pump.

Zero conveyance/Lack of lubrication:

At this operating point safe operation of the pump
can no longer be guaranteed; in this case the
flushing circuit and the lubrication of the bearings
may be suddenly interrupted by overheating and
evaporation of the enclosed medium.

Sudden condition change:

Basic setting: Fluctuations of more than 20% of the
design torque (Q

opt

)

Drive stoppage:

In operation with overloaded magnetic drive …not
admissible --- switch off immediately.

6.2.1 LEDs

Start:
All displays come on
Cold start 5 seconds
Warm start 3 seconds
Self-test:

If error, error position flashes (A-G or
temperature sensor)

Temperature sensor

flashing

Line interrupted

fast flashing

Short circuit or off

Sudden load change

flashing

Shortly before max. loading of
the magnetic drive

fast flashing

Drive stoppage

Direction of rotation

both flashing

No connection

Cable missing

both come on

Pump at standstill

green comes on

Clockwise

red comes on

Counterclockwise

Fig. 9

Flash when there is an error:
A

RAM

Main memory defective

B

ROM

Firmware defective

C

Clock

System time is wrong

D

FRAM

Data loss/defective

E

RFID

Data loss/defective,
not connected

F

Parameters

not present or defective

G flashing Performance curves not available
G

faster flashing Value error

A B

C

D

E

F G