Crown Boiler BSI172 User Manual

Page 25

Advertising
background image

25

24

16) Check the manifold pressure and adjust if necessary. To do this, use the following procedure:

a) Connect a manometer to the inlet pressure tap on the gas valve (see Figures 23 and 24).
b) Check the inlet pressure with all gas appliances on and off. The inlet pressure at the boiler must be within the

following limits regardless of what combination of appliances is firing:

Inlet Press (inches w.c.)

Natural Gas

LP Gas

Min.

5.0

11.0

Max.

14.0

13.0

If the inlet pressure falls outside of these limits, find and correct the cause of the problem before proceeding further.

c) Connect a manometer to the manifold (outlet) pressure tap on the gas valve (see Figures 23 and 24).
d) Read the manifold pressure. It should be set at:

Natural Gas

LP Gas

Manifold Press. (inches w.c.)

3.5

10.0

e) If a manifold pressure adjustment is needed, make the adjustment by turning the pressure regulator (see Figures 23

and 24) screw clockwise to raise the pressure and counter clockwise to reduce the pressure. If a manifold pressure
adjustment is made, recheck the line pressure to be certain that it is still within acceptable limits. Replace the cover
screw on the regulator.

WARNING

FAILURE TO FOLLOW THE FOLLOWING PROCEDURE EXACTLY COULD RESULT IN OVER-FIRING OF
THE BOILER AND A CARBON MONOXIDE HAZARD.

FIGURE 20: STANDING PILOT

BURNER FLAME

FIGURE 21: INTERMITTENT IGNITION

PILOT BURNER FLAME

Advertising
This manual is related to the following products: