Crown Boiler BSI172 User Manual

Page 38

Advertising
background image

38

37

Troubleshooting Chart for BSI Boilers Equipped with
McDonnell & Miller #67 Low Water Cut-offs and Vent Dampers
Caution
: Read page 34 before attempting to use this chart

Is there an audible

click as R8225 relay

pulls in w hen the

thermostat calls for

heat?

Does relay

pull in now ?

Vent

damper

open?

START

Thermostat

calls for heat

24 volts across

blue and yellow

w ires inside

junction box?

120 volts across

black and w hite

transformer

leads?

*Pow er off
*Blow n fuse or
tripped
breaker
*Misw ired or
loose 120 volt
connection

N

Y

* Defective
transformer
See Note #6 on
page 34

N

Y

* Bad connection in
thermostat w iring
* Defective thermostat
* Thermostat misw ired or
misapplied

N

N

24 volts

betw een terminal # 1

on 67 LWCO and
yellow tranformer

connection?

24 volts present

betw een each

pressure limit

connection and

yellow transformer

connection?

* Boiler off on pressure limit
* Defective pressure limit

Is 24 volts

present across

brow n and

yellow leads on

R8225 relay?

Disconnect
thermostat and
temporarily jump
boiler thermostat
connections
together

* Loose
connection
betw een
transformer
and R8225
coil

* Defective
R8225
See Note #7
on page 34

* Boiler off on low w ater

24 volts present

across blue lead on

R8225 and yellow

transformer leads?

* Defective R8225

Y

Y

N

N

Y

Y

Y

N

N

Y

Y

N

Advertising
This manual is related to the following products: