A. This appliance has a pilot which must be

lighted by hand. When lighting the pilot, follow
these instructions exactly.

B. BEFORE LIGHTING smell all around the

appliance area for gas. Be sure to smell next
to the floor because some gas is heavier than
air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.
Do not touch any electric switch; do not

use any phone in your building.

Immediately call your gas supplier from

a neighbor’s phone. Follow the gas
supplier’s instructions.

If you cannot reach your gas supplier, call

the fire department.

C. Use only your hand to push in or turn the gas

control knob. Never use tools. If the knob will

not push in or turn by hand, don’t try to repair it,
call a qualified service technician. Force or
attempted repair may result in a fire or explosion.

D. Do not use this appliance if any part has been

under water. Immediately call a qualified service
technician to inspect the appliance and to

replace any part of the control system and any

gas control which has been under water.

LIGHTING INSTRUCTIONS

1. STOP! Read the safety information above on

this label.

2. Set the thermostat to lowest setting.

3. Turn off all electric power to the appliance.

4. Remove front access panel.

5. Rotate the gas control knob clockwise to OFF.

8. Turn Knob on gas control counterclockwise

to “PILOT”.

9. Push down and hold the red reset button while

you light pilot burner with a match.

After about one minute, release reset button.

Pilot should remain lit. If it goes out, turn gas

control knob clockwise to OFF. To relight,

repeat steps 5-9.
If button does not pop up when released, stop

and immediately call your service technician

or gas supplier.

If the pilot will not stay lit after several tries,

turn the gas control knob to “OFF” and call

your service technician or gas supplier.

10. After pilot remains lit when red reset button is

released, turn gas control knob counterclockwise

to ON.

11. Replace front access panel.

12. Turn on all electric power to the appliance.

13. Set thermostat to desired setting.

1. Set the thermostat to lowest setting.

2. Turn off all electric power to the appliance if
service is to be performed.

3. Push in gas control knob slightly and turn
clockwise to “OFF”. Do not Force.

WARNING: If you do not follow these instructions exactly, a fire or explosion

may result causing property damage, personal injury or loss of life.

6. Wait five (5) minutes to clear out any gas. Then

smell for gas, including near the floor. If you then

smell gas, STOP! Follow “B” in the safety inform-

ation above on this label. If you don’t smell gas,

go to the next step.

7. Find pilot - follow metal pilot

tube from gas control to

pilot burner.

146-80-254 Rev. 0

(Standing Pilot)

PILOT

BURNER

THERMO-

COUPLE

TO TURN OFF GAS TO APPLIANCE

FOR YOUR SAFETY READ BEFORE OPERATING

RESET BUTTON

GAS INLET

GAS CONTROL KNOB
(SHOWN IN “ON” POSITION)

GAS OUTLET

GAS VALVE - TOP VIEW

LIGHTING INSTRUCTIONS FOR BOILERS EQUIPPED WITH HONEYWELL

VR8200 AND VR8300 SERIES GAS VALVES (STANDING PILOT)

Advertising