tekmar 370 House Control User Manual

Page 15

Advertising
background image

Copyright © D 370 -06/99

15 of 20

Minimum Boiler Supply











Most boilers require a minimum operating temperature to prevent corrosion from flue gas
condensation. The

Min. Boiler Supply dial should be set to the lowest supply water

temperature at which the boiler can operate without causing the boiler flue gases to
condense. Consult the boiler manufacturer for recommended minimum boiler supply
temperatures. Some typical settings are given below. If a condensing or electric boiler is
used, the

Min. Boiler Supply dial can be set to Off.

Typical settings:

• Steel fire tube boilers . . . . . . 140 to 160

°F (60 to 71°C)

• Cast iron boilers . . . . . . . . . . 135 to 160

°F (57 to 71°C)

• Copper tube boilers . . . . . . . 135 to 150

°F (57 to 66°C)

Maximum System Supply

−

−

−

−

−

If the 370 is used in

Boiler mode, the 370 helps prevent the boiler supply water

temperature from rising above the

Max. System Supply dial setting. If the 370 is used

in

Mixing mode, the 370 helps prevent the mixed supply water temperature from

rising above the

Max. System Supply dial setting. The Max. System Supply dial should

be set to the maximum temperature allowed in the system loop. There are many
factors which may limit the allowable supply temperature in a radiant floor heating slab.
A few of these are provided below.

• Some tubing manufacturers recommend that their products not be maintained at

temperatures exceeding 140

°F (60°C). Consult the tubing manufacturer for

specific details.

• No where in the concrete should the temperature be maintained above 170

°F (77°C).

• The surface temperature of a radiant floor heating slab should normally not exceed

85

°F (29°C). The slab surface temperature is affected by the slab thermal resistance

and the supply water temperature to the slab.

Unoccupied Temperature

−−−−−−−−−−−

−−−−−−−−−−−

−−−−−−−−−−−

−−−−−−−−−−−

−−−−−−−−−−−

The

UnOccupied dial sets the desired indoor temperature during UnOccupied (Night

Setback) mode. When a Zone Control is used, the zones connected to the Zone Control
are not affected by the

UnOccupied dial on the 370. The Zone Control has its own

UnOccupied mode which is explained in more detail in the Data Brochure supplied with
the Zone Control.

Heating Curve

−−−−−−−−−−−−−

−−−−−−−−−−−−−

−−−−−−−−−−−−−

−−−−−−−−−−−−−

−−−−−−−−−−−−−

The

Heating Curve dial setting determines the number of degrees the supply water

temperature is raised for every one degree drop in outdoor temperature. The

Heating

Curve dial position can be calculated from the following formula.

design supply temperature – desired room temperature

Heating Curve =



desired room temperature – design outdoor temperature

Example: A system is designed to supply 120

°F (49°C) water when the outdoor

temperature is 10

°F (-12°C). The desired room temperature is 70°F (21°C).

120 - 70

°F (49 - 21°C)

50

°F (28°C)

Heating Curve

=



=

 = 0.8

70 - 10

°F (21 - (-12)°C)

60

°F (16°C)

If the design supply water temperature is unknown, the

Heating Curve dial can be set to

a trial value using the typical design supply water temperatures given below.

Typical design supply temperatures:

• Hydronic radiant floors …......100 to 130

°F (38 to 54°C)

• Baseboard radiators …..........160 to 190

°F (71 to 88°C)

• Fan coils …............................180 to 210

°F (82 to 99°C)

DIP Switch Settings

−

−

−

−

−

Max. System

Supply

120

170

°F

220

130

°F

Off

165

Min. Boiler

Supply

100

70

°F

(21

°C)

40
(4)

100

(38)

UnOccupied

0.2

2

3.6

1

3

Heating Curve

Outdoor air temperature

50

(10)

30

(-1)

10

(-12)

-10

(-23)

70

(21)

3.6 3.0 2.4 2.0

1.6

1.2

0.8

0.4

1.0

0.6

90

(32)

WWSD

Point

°F

(

°C)

Supply water temperature

110

(43)

70

(21)

90

(32)

210

(99)

170

(77)

150

(65)

130

(54)

190

(88)

0.2

Settings

Advertising