Sequence of operation – tekmar 370 House Control User Manual

Page 6

Advertising
background image

Copyright © D 370 -06/99

6 of 20

Sequence of Operation

POWERING UP THE CONTROL

After the House Control 370 is powered up, a software version code is displayed for 2
seconds and then the red indicator lights are turned on for 4 seconds. When the control is
powered up, the green

Power light remains on continuously. For the first fifteen minutes

after power up, the

Test light flashes and the control responds immediately to changes of

settings. This allows the installer to test the operation of the system. After 15 minutes the
control enters its normal operating mode in which reactions to setting changes are
significantly slower. A slower reaction time to setting changes allows the control to provide
a stable room temperature.

WARM WEATHER SHUT DOWN (WWSD)

When the outdoor temperature rises above the highest Room Temperature Unit (RTU) dial
setting and all heating zones are satisfied, the

WWSD light is turned on and the variable

speed injection pump and all zone relays are turned off. If the system pump is not required
for a DHW operation, the system pump is also turned off. When an external Zone Control
input is used, the

WWSD light is only turned on when all the zones connected to the 370

and all the zones connected to the Zone Control are satisfied.

BOILER OPERATION

If the DIP switch is set to

Boiler, the system supply water temperature is controlled by turning

the boiler on and off. An outdoor reset strategy is used with indoor temperature feedback from
each of the 4 zones. The boiler differential is automatically calculated. When the 370 control
is used in the boiler mode (DIP switch set to

Boiler ), the boiler sensor must be installed on

the supply pipe of the boiler, and the boiler sensor DIP switch must be set to

Boiler Supply.

If the boiler sensor DIP switch is set to

Boiler Return, a combination of LEDs will flash, as

shown in the error message table, to indicate an illegal DIP switch setting. To eliminate the
error message, simply set the boiler sensor DIP switch to

Boiler Supply.

Maximum Boiler Supply

−−−−−−−−−−−−−−−−−−−−−−−−−−

−−−−−−−−−−−−−−−−−−−−−−−−−−

−−−−−−−−−−−−−−−−−−−−−−−−−−

−−−−−−−−−−−−−−−−−−−−−−−−−−

−−−−−−−−−−−−−−−−−−−−−−−−−−

The 370 has a

Max. System Supply dial that can be used to set a maximum boiler supply

water temperature. If the supply water temperature approaches the

Max. System Supply

dial setting, the

Maximum Supply light is turned on and the 370 operates the boiler at one

differential below the

Max. System Supply setting. At no time does the control allow the

target boiler supply temperature to exceed 212

°F (100°C).

Minimum Boiler Supply











The 370 has a

Min. Boiler Supply dial which sets a minimum target boiler

supply temperature. This dial has an

Off position for condensing and

electric boilers. If the boiler is fired and the boiler supply temperature is
near or below the

Min. Boiler Supply dial setting, the 370 turns on the

Minimum Boiler light and reduces the heating load on the boiler. During
this warm up period, some of the zones may be prevented
from operating until the boiler supply water is at the required
minimum temperature.

MIXING OPERATION

If the DIP switch is set to

Mixing, the system supply water temperature is

controlled by varying the speed of an injection pump. See Essay E 021 for
more information. An outdoor reset strategy is used with indoor temperature
feedback from each of the 4 zones.

Boiler Control











When both a Supply and Boiler Sensor are present and located on the
mixed supply and boiler supply piping, the DIP switches must be set to
Boiler Supply and Mixing. The 370 controls the boiler directly and
automatically calculates the required boiler differential. The boiler
aquastat (limit) should be set at least 20

°F (11°C) higher than

boiler design.

Boiler Load Reset











As the heating load on the mixed loop increases, the speed of the
variable speed injection pump increases. Over time, the 370 also raises
the boiler temperature to satisfy this increased heating load. The 370
also ensures the target boiler supply temperature is above the

Min.

Boiler Supply dial setting, but does not exceed 212

°F (100°C).

Only in the first 15 minutes after power up, does

the control respond immediatley to settings

adjustments.

70

M

Test

Max. System

Supply

120

170

°F

220

Maximum
Supply

M

M

WWSD

M

M

Sensor

Minimum
Boiler

130

°F

Off

165

Min. Boiler

Supply

100

M

M

Sensor

Boiler

Boiler

Mixing

Operation

Supply

Sensor

130

°F

Off

165

Min. Boiler

Supply

100

Boil

Sensor

Mixing

Boiler Supply