2.05 INPUT WIRING SPECIFICATIONS
CutMaster A40 Power Supply Input Cable Wiring Requirements
Input voltage
Freq
Power Input
Suggested Sizes
Volts
Hz
kVA
I max
I1eff
Fuse (amps)
Flexible Cord
(Min. AWG)
1 Phase
208
60
10.4
47
30
50
10
230
60
10.8
45
29
50
10
460
60
15.2
31
20
35
12
3 Phase
208
60
5.4
26
17
30
12
230
50/60
5.8
24
16
30
12
380
50/60
6.1
16
11
20
14
400
50/60
6.4
16
11
20
14
460
60
7.4
16
10
20
12
600
60
7.8
13
11
15
12
Line Voltages with Suggested Circuit Protection and Wire Sizes
Based on National Electric Code and Canadian Electric Code
NOTE
Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.
Cable size is de-rated based on the Duty Cycle of the equipment.
The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installations
refer to local or national codes.
An energy limiting fuse UL Class RK-1 (examples: BUSS LPS/LPN-RK or Gould-Shawmut AZK-A6K) should be used
to minimize damage to Plasma Cutting, Welding or power distribution equipment.
NEVER use replaceable element fuses like UL Class H, or “one-time” fuses like UL Class K5.