INSTALLATION PROCEDURES

16

Manual 0-2478

Remote Control

PC Board Assembly

A-00679

E1

J6

Figure 3-11 OK-To-Move Jumper Location

A jumper wire is connected between the terminal block
J6 and the lug connection E1 on the PC board. Select the
proper operation by moving the end of the wire connected
to the terminal block per the following chart:

O K-T o -M ove Se le ct io n

J6

D ry C on t a ct s

1 4 *

2 4 VAC

1 5

* = F a ct o ry Se t t in g

The Remote Control supplies an isolated OK-To-Move
signal. The signal may be selected to be a relay contact
closure that closes to signal motion start or a 24 VAC sig-
nal.

NOTE

When using the Remote Control the OK-To-Move
signal in the Control Module should be set for con-
tacts. Refer to the Control and Power Components
Operating Manual supplied with the Control Mod-
ule.

The OK-To-Move signal is available at the Remote Con-
trol rear panel CNC connector, J29 pins 12 and 14, or at
the internal CNC connection, J6 pins 13 and 16. The con-
tacts are normally closed (NC) when power is OFF. When
power is turned ON the contacts open if the following
conditions are met:

• ENABLE switch is ON

• STATION SELECT switch is active

Contacts close when arc transfers to signal OK-To-Move.

To select contact closure connect the E1 jumper to termi-
nal block J6 position 14.

A-00716

13

15

16

E1

Jumper

Wire

NC

J29-12

J6-13

J6-16

J29-14

J6

Contact Closure

Wiring Diagram

Figure 3-12 Wiring Using Contact Closure

To select 24 VAC connect the E1 jumper to terminal block
J6 position 15.

A-00717

13

14

16

E1

Jumper

Wire

NC

J29-12

J6-13

J6-16

J29-14

J6

24 VAC

Contact Closure

Wiring Diagram

Figure 3-13 Wiring Using 24 VAC

For cutting systems using two or more plasma supplies it
is neccessary to connect the OK-To-Move in each Remote
Control to both turn ON to get the proper motion signal.
If the units turn ON at different times then motion may
start before the second plasma transfers. It is recom-
mended that the OK-To-Move contacts be connected per
the following:

Using Contact Closure Only

Connect the OK-To-Move contacts in series. Both con-
tacts need to be closed, normal condition, to have a com-
pleted circuit. When one plasma supply is not being used,
either by the plasma power supply power, STATION
SELECT, or ENABLE are turned OFF, the contact closure