Appendix 1: input wiring requirements – Tweco FP-82 User Manual

Page 35

Advertising
background image

Manual 0-2870

A-1

APPENDIX

APPENDIX 1: INPUT WIRING REQUIREMENTS

NOTES

Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.

Cable size is de-rated based on the Duty Cycle of the equipment.

The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installations refer
to local or national codes.

Cable conductor temperature used is 167° F (75° C).

An energy limiting fuse UL Class RK-1 (examples: BUSS LPS/LPN-RK or Gould-Shawmut AZK-A6K) should be
used to minimize damage to Plasma Cutting, Welding or power distribution equipment.

NEVER

use replaceable element fuses like UL Class H, or "one-time" fuses like UL Class K5.

Input

Power Input

Current Input

Suggested Sizes (See Notes)

Voltage

Freq.

1-Ph

3-Ph

1-Ph

3-Ph

Fuse (Amps)

Wire (AWG)

Wire (Canada)

(Volts)

(Hz)

(kVA)

(kVA)

(Amps) (Amps)

1-Ph

3-Ph

1-Ph

3-Ph

1-Ph

3-Ph

208

50/60

11.8

57

60

6

6

230

50/60

11.8

52

50

6

6

Line Voltages with Suggested Circuit Protection and Wire Sizes

Based on National Electric Code and Canadian Electrical Code

FirePower FP-82 Input Wiring Requirements

Advertising