13 removing the handle from a p type valve, Figure 5: manual valve on a standoff, Figure 6: p type valve with an svh handle 6 – VICI Two position Standard electric User Manual

Page 8

Advertising
background image

4.13 Removing the Handle from a P Type Valve

These types of valves have a 1-1/8" metal rotor shaft that connects to the handle.

1.

Rotate the knob counterclockwise so the valve is positioned properly for
later installation on the electric actuator.

2.

See Figure 6. Remove the black handle by sliding its shaft out of the
coupling.

3.

Place the coupling in a bench vise with the side with only one hole facing
up. Use a hammer and punch to remove the roll pin which connects the
coupling to the valve rotor shaft. Pull the coupling off of the shaft.

CAUTION: Do not hold the valve body in the vise when removing the
coupling. Valve damage will result.

4.

Proceed to Section 4.2 for closemount assembly, or Section 4.3 if the valve
will go on a standoff before being installed on the actuator.

KNOB ASSEMBLY

STANDOFF ASSEMBLY (Length varies)

WITH VALVE ATTACHED

WK/KNOB

RETAINER

HWSC-SS8-5B/

SET-SCREW

MHA/MANUAL

HANDLE

ADAPTER

FLAT FACE

SCREWS
FOR CR2

(NOT SUPPLIED)

HWSC-SC6-8B/

SCREW

STANDOFF

OPTIONAL

MOUNTING

BRACKET OR

OVEN WALL

PRE-LOAD
ASSEMBLY

VALVE

BODY

Figure 5: Manual valve on a standoff

SPRING HARDWARE

(Varies with valve type)

VALVE

BODY

CUTOUT

ROTOR

PIN

ROLL
PIN

COUPLING

SHAFT

FLAT

FACE

SVH/
STANDARD
HANDLE

HWSC-SS10-3B/

SET-SCREW

HANDLE ASSEMBLY

Figure 6: P Type valve with an SVH handle