Optional serial interface, Establishing serial communication – VICI EUT Universal Electric Actuator User Manual

Page 10

Advertising
background image

6

Optional Serial Interface

Note: Models with product numbers ending in “A” have been factory-set for RS-232; those
ending in “F” were set for RS-485. If you wish to convert an “A” model to an “F” model or
vice versa, refer to “Setting the Serial Port Configuration Switch” on page 9.

Establishing Serial Communication

Serial communication requires a terminal
emulation or communication software (such
as HyperTerminal

®

, included with Windows

®

)

running on a PC-compatible computer. Set
the serial port at 9600 baud, no parity, 8 data
bits, 1 stop bit, no hardware or software
handshaking.

With the software running, check the bi-direc-
tional communication link between the keyboard/monitor
of the computer and the serial port by typing /?<enter>. If
the link is functioning, the following menu will appear on
your monitor:

Control Command List

GO[nn]

- Move to nn position

HM

- Move to the first Position

CW[nn]

- Move Clockwise to nn Position

CC[nn]

- Move Counter Clockwise to nn Position

TO

- Toggle Position to Opposite

TT

- Timed Toggle

DT[nnnnn]

- Set Delay time for TT Command

CP

- Returns Current Position

AM[n]

- Sets the Actuator Mode [1] Two Position With Stops,

[2] Two Position Without Stops, [3] Multi Position

SB[nnnn]

- Set the Baud Rate to nnnnn

ID[nn]

- Set Device ID nn=(0-9, A-Z)

*ID*

- Reset ID to none

NP[nn]

- Set the Number of Positions to nn

SM[n]

- Set the Direction [F]orward, [R]everse, [A]uto

LRN

- Learn Stops Location

CNT[nnnnn]

- Set Cycle Counter

VR

- Firmware Version(s)

/?

- Displays This List

Figure 7: Serial connectors

on rear panel

SERIAL

A

B

RS-232

CONNECTIONS

Advertising