8. DATASTICK COMMS MENU

The DATASTICK Comms Menu is currently not operational with the 2020
ClearTrace System.

9. ANALOG OUTPUT(S)

The analog output menu is used to setup the 4milliamp to 20 milliamp
analog output in the AV38. This function allows the following
assignments:

Parameter: Assign either turbidity or temperature to the output.

4mA Value: Assign the lowest value of turbidity or temperature to be
reported.

20mA Value: Assign the highest value of turbidity or temperature to
be reported.

Calibrate: Use an external ammeter to calibrate the output for precise
current readings.

When the AV38 is
configured with two current
outputs then the main menu
list shows “Analog Output 1”
and “Analog Output 2” The
menu system for each output
is identical.
Note: During calibration, the
analog output is held at its
present value.
The complete analog output
menu is shown in 8.1.

To configure the Analog
Output, select it from the
main menu by pressing
ENTER.

To view or reassign the
parameter driving the output
(turbidity or temperature),
select “Set Parameter” with
the ENTER key.

27

Main Menu
Analog Output

MENU

ESC

ENTER

t

t

t

t

t

Analog Output
Set Parameter

MENU

ESC

ENTER

Set 4mA Value
Set 20mA Value
Calibrate
Exit

t

t

t

t

t
t

t

t

t

Analog Output
Set Parameter

MENU

ESC

ENTER

t

t

t

t

t

Figure 8.1 Analog output menu