70

UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal

injury or death.
Disconnect gas piping from unit when leak testing at

pressure greater than 1/2 psig. Pressures greater than

1/2 psig will cause gas valve damage resulting in

hazardous condition. If gas valve is subjected to

pressure greater than 1/2 psig, it must be replaced

before use. When pressure testing field--supplied gas

piping at pressures of 1/2 psig or less, a unit connected

to such piping must be isolated by manually closing

the gas valve.

!

WARNING

Return--Air Filters

Make sure correct filters are installed in unit (see

Appendix II -- Physical Data). Do not operate unit without

return--air filters.

Outdoor--Air Inlet Screens

Outdoor--air inlet screen must be in place before operating

unit.

Compressor Mounting

Compressors are internally spring mounted. Do not loosen

or remove compressor hold down bolts.

Internal Wiring

Check all factory and field electrical connections for

tightness. Tighten as required.

Refrigerant Service Ports

Each unit system has two 1/4” SAE flare (with check

valves) service ports: one on the suction line, and one on

the compressor discharge line. Be sure that caps on the

ports are tight.

Compressor Rotation

On 3--phase units with scroll compressors, it is important

to be certain compressor is rotating in the proper

direction. To determine whether or not compressor is

rotating in the proper direction:

1. Connect service gauges to suction and discharge

pressure fittings.

2. Energize the compressor.
3. The suction pressure should drop and the discharge

pressure should rise, as is normal on any start--up.

If the suction pressure does not drop and the discharge

pressure does not rise to normal levels:

4. Note that the evaporator fan is probably also rotating

in the wrong direction.

5. Turn off power to the unit and install lockout tag.
6. Reverse any two of the unit power leads.
7. Re--energize to the compressor. Check pressures.

The suction and discharge pressure levels should now

move to their normal start--up levels.

NOTE: When the compressor is rotating in the wrong

direction, the unit will make an elevated level of noise
and will not provide cooling.

Cooling

Set space thermostat to OFF position. To start unit, turn on

main power supply. Set system selector switch at COOL

position and fan switch at AUTO. position. Adjust

thermostat to a setting approximately 5_F (3_C) below

room temperature. Both compressors start on closure of

contactors.

Check unit charge. Refer to Refrigerant Charge section.

Reset thermostat at a position above room temperature.

Both compressors will shut off. Evaporator fan will shut

off immediately.

To shut off unit, set system selector switch at OFF

position. Resetting thermostat at a position above room

temperature shuts unit off temporarily until space

temperature exceeds thermostat setting.

Main Burners

Main burners are factory set and should require no

adjustment.

To check ignition of main burners and heating controls,

move thermostat setpoint above room temperature and

verify that the burners light and evaporator fan is

energized. Check heating effect, then lower the thermostat

setting below the room temperature and verify that the

burners and evaporator fan turn off.

Refer to Table 11 for the correct orifice to use at high

altitudes.

Heating

1. Purge gas supply line of air by opening union ahead

of the gas valve. If gas odor is detected, tighten union

and wait 5 minutes before proceeding.

2. Turn on electrical supply and manual gas valve.
3. Set system switch selector at HEAT position and fan

switch at AUTO. or ON position. Set heating

temperature lever above room temperature.

4. The induced--draft motor will start.
5. After a call for heating, the main burners should light

within 5 seconds. If the burner does not light, then

there is a 22--second delay before another 5--second

try. If the burner still does not light, the time delay is

repeated. If the burner does not light within 15

minutes, there is a lockout. To reset the control, break

the 24 v power to W1.

6. The evaporator--fan motor will turn on 45 seconds

after burner ignition.

7. The evaporator--fan motor will turn off in 45 seconds

after the thermostat temperature is satisfied.

8. Adjust airflow to obtain a temperature rise within the

range specified on the unit nameplate.

48TC