14: After installing the entire low voltage system, if the lamps
have low intensity, then measure the voltage at the fixture
closest to the power feed contacts with a voltmeter. The
system must be at least 80% loaded and the voltmeter
should read between 11V-12V ~AC. If the voltage does not
fall in this range, call Edge Lighting "Technical Support" at
773-770-1195.

15: After operating the system for a few minutes, on the low
voltage side, all electrical connection points should be no
more than warm to the touch. If a connection is hot to the
touch, retighten the connection and check to ensure that
the temperature decreases.

16: The transformer circuit breaker will trip if there is a short in
the system. After removing the cause of the short, reset
the circuit breaker to power the system.

17: Replace the transformer cover and tighten the two Phillips
screws on the sides of the transformer.