Terminal tap chart – Edge Lighting 600W/12V Dual Feed Magnetic Remote Transformer User Manual
Page 3
3
C
7: Install a conduit from the transformer to the electrical box.
8: For the best performance, use the "Low Voltage Wire Size
Chart" on page 2 to select the wire size.
NOTE: The THHN wire sizes specified in "Low Voltage Wire Size
Chart" are for 3% or less drop in voltage based on 300 watt
loads. Lengths are the distance from the remote transformer to
the system power feed connector, or power feed canopy.
9: Install the THHN low voltage wires from the transformer to
the electrical box where the power feed canopy will be
installed.
10: Insert one low voltage wire into the "COMT" terminal and
tighten the screw firmly. Mark this low voltage wire in the
electrical box as "COM1".
11: Insert the second low voltage wire into the "T2" terminal
and tighten the screw firmly. Mark this low voltage wire in
the electrical box as "HOT1".
12: Insert the third low voltage wire into the "COMP" terminal
and tighten the screw firmly. Mark this low voltage wire in
the electrical box as "COM2".
13: Insert the fourth low voltage wire into the "P2" terminal
and tighten the screw firmly. Mark this low voltage wire in
the electrical box as "HOT2".
14: Connect the 120 volt power wires at the panel.
15: Measure the voltage at the power wires coming into the
transformer. If the voltage is not in the range of 115-120
volt, then pick the proper terminal tap using the "Terminal
Tap Chart" below to reconnect the second and fourth low
voltage wires.
NOTE: Risk of Fire - The terminal taps ARE NOT for boosting
the transformer low voltage power, they are selected to ensure
output power voltage based upon input power voltage condition.
NEVER use a higher terminal tap to compensate for voltage
drop, this will overheat the low voltage wires and transformer. It
is recommended to use the wire size as indicated in "Low
Voltage Wire Size Chart" on page 2 to avoid excessive voltage
drop.
COMT T1
T2
T3
T4 COMP P1
P2
P3
P4
COM1
COM2
HOT1
HO
T2
ELECTRICAL BOX
7
CONDUIT
9
14
15
9
13
12
10
11
TERMINAL TAP CHART
PRIMARY POWER
INPUT VOLTAGE
TERMINAL TAP
TO BE USED
T4
T3
T2
T1
TERMINAL TAP
TO BE USED
P4
P3
P2
P1
105-109
110-114
115-120
121-125
NOTE: Using a smaller wire size other than specified will result in
a increase in voltage drop and will reduce the lamp intensity.