Accessory Electric Heaters Installation

Electric heaters may be installed with the 50JZ--A units per

instructions supplied with electric heater package. See unit rating
plate for factory--approved electric heater kits.

Sequence of Operation

a. CONTINUOUS FAN

(1.) Thermostat closes circuit R to G energizing the

blower motor for continuous fan.

b. COOLING MODE

(1.) If indoor temperature is above temperature set

point, thermostat closes circuits R to G, R to Y1

and R to O (Y2). The compressor, indoor and
outdoor fans, and reversing valve are energized.

c. ELECTRIC HEATING MODE

(1.) Thermostat closes circuit R to W/W1, or W2 and R
to G. There are no on or off delays.

d. HEAT PUMP HEATING MODE

(1.) Thermostat closes circuits R to G and R to Y1. The

compressor, indoor and outdoor fans are energized.

e. HEAT PUMP HEATING WITH AUXILIARY

ELECTRIC HEAT

(1.) Thermostat closes circuits R to G, R to Y1 and R

to W/W1 or W2. The compressor, indoor and

outdoor fans are energized, as well as the electric
heat relays.

f. DEFROST MODE

The defrost mode is automatically energized by the
defrost board during heating mode. The defrost board

energizes “O” (reversing valve) and “W2” (electric
heat). It also de--energizes the outdoor fan. When defrost
is complete, unit will return to heating mode. If room

thermostat is satisfied during defrost, unit will shut
down and restart in defrost on next call for heat.

INDOOR
THERMOSTAT

DISCONNECT
PER NEC

FROM
POWER
SOURCE

RETURN
AIR

TOP COVER

POWER ENTRY

CONTROL ENTRY

A09098

Fig. 11 -- Typical Installation

Table 2 – Minimum Airflow for Reliable Electric Heater Operation (CFM)

SIZE

50JZ--A24

50JZ--A30

50JZ--A36

50JZ--A48

AIRFLOW (CFM)

800

1000

1200

1600

AIRFLOW (L/s)

378

472

567

756