Carrier MODULINE 37HS User Manual
Page 36

Table 10 — Minimum Static Pressure at Control
(Master) Unit — Units with System-Powered
Controls and Standard Diffusers
AIRFLOW
(Cfm)
37HS1
37HS2
37HS4
PLENUM SIZE (in.)
7 x 7
7 x 7
9 x 9
5 x 7
9 x 9
9 x 9
11 x 11
11 x 11
11 x 11
13 x 13
Minimum Static Pressure (in. wg)
40
0.75
0.75
N/A
N/A
50
60
70
80
0.75
0.75
0.75
N/A
90
100
110
0.90
0.90
0.75
N/A
120
N/A
N/A
0.75
N/A
140
160
N/A
N/A
0.75
0.75
180
200
220
N/A
N/A
0.90
0.75
240
N/A
N/A
N/A
0.75
280
320
360
400
440
N/A
N/A
N/A
0.90
N/A — Not Applicable
NOTE: Maximum inlet pressure — 3.0 in. wg.
Table 11 — Additional
⌬
P for
Extended Lengths of Flexible Duct
FLEX
DUCT
DIAM
(in.)
TOTAL
CFM
IN AIR
SERIES
ADDITIONAL
⌬
P PER
10 FT FLEX DUCT
(in. wg)
6
400
0.2
8
800
0.16
10
1100
0.1
12
1600
0.07
Table 12 — Additional
⌬
P for
Flexible Duct with 90-Degree Bend
FLEX
DUCT
DIAM
(in.)
TOTAL
CFM
IN AIR
SERIES
RADIUS
OF
BEND
(in.)
ADDITIONAL
⌬
P
FOR 90° BEND
IN FLEXIBLE DUCT
(in. wg)
6
400
18
0.26
8
800
24
0.16
10
1100
30
0.08
12
1600
36
0.04
C — Controller
Fig. 23 — Three 37HS2 Moduline
ா
Units in Adjoining Modules
Fig. 24 — Four 37HS2 Moduline Units in Alternate Series Modules
36