Carrier 48TF004-007 User Manual

Page 6

Advertising
background image

6

Table 1 — Physical Data — 48TF004-007 (cont)

LEGEND

*Evaporator coil fin material/condenser coil fin material. Contact your local

representative for details about coated fins.

†Weight of 14-in. roof curb.

**Single phase/three-phase.

††Rollout switch lockout is manually reset by interrupting power to unit or

resetting thermostat.

|| Single-phase units have a single-stage gas valve. The heating input values

are as follows:

48TFF004, 115,000 Btuh
48TFF005, 150,000 Btuh
48TFF006, 150,000 Btuh

NOTE: High-static motor not available on single-phase units.

UNIT SIZE 48TF

E/F/M/N004

D/E/F/L/M/N005

D/E/F/L/M/N006

D/E/F007

FURNACE SECTION

Rollout Switch Cutout
Temp (F)††

195

195

195

195

Burner Orifice Diameter
(in. ...drill size)

Natural Gas

Std

TFD

—

.113...33

.113...33

.113...33

TFE

.113...33

.113...33

.113...33

.113...33

TFF

.113...33

.129...30

.129...30

.129...30

TFL

—

.102...38

.102...38

—

TFM

.102...38

.102...38

.102...38

—

TFN

.102...38

.116...32

.116...32

—

Liquid Propane

Alt

TFD

—

.089...43

.089...43

.089...43

TFE

.089...43

.089...43

.089...43

.089...43

TFF

.089...43

.102...38

.102...38

.102...38

TFL

—

.082...45

.082...45

—

TFM

.082...45

.082...45

.082...45

—

TFN

.082...45

.089...43

.089...43

—

Thermostat Heat Anticipator
Setting (amps)

208/230 v and 575

Stage 1

.14

.14

.14

.14

Stage 2

.14

.14

.14

.14

460 v

Stage 1

.14

.14

.14

.14

Stage 2

.14

.14

.14

.14

Gas Input (Btuh)||

Stage 1

TFD

—

72,000

72,000

72,000

TFE

72,000

115,000

115,000

115,000

TFF

82,000

120,000

120,000

120,000

TFL

—

60,000

60,000

—

TFM

60,000

90,000

90,000

—

TFN

90,000

120,000

120,000

—

Stage 2
(3-phase units)

TFF

115,000

150,000

150,000

150,000

Efficiency (Steady

State) (%)

80

80

80

80

Temperature Rise Range

TFD

—

25-55

25-55

25-55

TFE

25-55

35-65

35-65

35-65

TFF

55-85

50-80

50-80

50-80

TFL

—

20-50

20-50

—

TFM

20-50

30-60

30-60

—

TFN

30-60

40-70

40-70

—

Manifold Pressure (in. wg)

Natural Gas

Std

3.5

3.5

3.5

3.5

Liquid Propane

Alt

3.5

3.5

3.5

3.5

Gas Valve Quantity

1

1

1

1

Gas Valve Pressure Range

Psig

0.180-0.487

0.180-0.487

0.180-0.487

0.180-0.487

in. wg

5.0-13.5

5.0-13.5

5.0-13.5

5.0-13.5

Field Gas Connection
Size (in.)

1

/

2

1

/

2

1

/

2

1

/

2

HIGH-PRESSURE SWITCH (psig)

Standard Compressor

450 ± 50

500 ± 50

Internal Relief (Differential)
Cutout

428

428

Reset (Auto.)

320

320

LOSS-OF-CHARGE (LOW-
PRESSURE SWITCH) (psig)

7 ± 3

Cutout
Reset (Auto.)

22 ± 7

FREEZE PROTECTION
THERMOSTAT (F)

Opens

30 ± 5

Closes

45 ± 5

OUTDOOR-AIR INLET SCREENS

Cleanable

Quantity...Size (in.)

1...20 x 24 x 1

RETURN-AIR FILTERS

Throwaway

Quantity...Size (in.)

2...16 x 25 x 2

Al

—

Aluminum

Bhp —

Brake Horsepower

Cu

—

Copper