30ra/30rh, Troubleshooting, Gb - 14 – Carrier AQUASNAP 30RH User Manual

Page 15

Advertising
background image

30RA/30RH

GB - 14

Troubleshooting

A list of possible faults, as well as the probable cause and
suggested solutions is shown as follows. In the event of a unit
malfunction it is recommended to disconnect the power supply and
ascertain the cause.

Symptoms

Cause

REMEDY

Unit does not start:

- No power supply;

CONNECT

POWER

SUPPLY

.

- Main switch open;

CLOSE

SWITCH

.

- Low line voltage;

CHECK

VOLTAGE

AND

REMEDY

THE

DEFICIENCY

.

- A protection has tripped;

RESET

.

- Contactor stuck open;

CHECK

AND

IF

NECESSARY

REPLACE

CONTACTOR

.

- Seized compressor;

CHECK

AND

IF

NECESSARY

REPLACE

COMPRESSOR

.

- Loose electrical connections;

CHECK

CONNECTIONS

.

Unit runs continuously or starts and stops frequently:

- Defective compressor contactor;

-

CHECK

AND

IF

NECESSARY

REPLACE

CONTACTOR

.

- Defective compressor;

CHECK

AND

IF

NECESSARY

REPLACE

COMPRESSOR

.

- Refrigerant losses;

CHECK

AND

ADD

THE

NECESSARY

QUANTITY

.

- Total water flow too low

CHECK

FOR

PRESSURE

DROP

IN

THE

HYDRAULIC

CIRCUIT

.

-

Static pressure in the hydraulic circuit too low;

CHECK

IT

ON

THE

PRESSURE

GAUGE

AND

RESTORE

IT

IF

NECESSARY

.

Unit continuously cuts out at low pressure:

- Refrigerant losses;

CHECK

AND

ADD

THE

NECESSARY

QUANTITY

.

- Low water flow in the exchanger;

CHECK

WATER

PUMP

.

- Unit start-up delay;

WAIT

UNTIL

THE

SYSTEM

HAS

STABILISED

.

Unit continuously cuts out at high pressure:

- Defective high pressurestat;

CHECK

AND

IF

NECESSARY

REPLACE

PRESSURESTAT

.

- Blocked expansion valve;

CHECK

AND

REPLACE

IF

NECESSARY

.

- Blocked filter drier;

CHECK

AND

IF

NECESSARY

REPLACE

FILTER

.

- The outdoor fan/s does/do not work;

CHECK

THE

CONDITION

OF

THE

FAN

MOTOR

/

S

AND

ITS

/

THEIR

ELECTRICAL

CONNECTIONS

.

-

Obstructed or dirty battery;

REMOVE

THE

OBSTRUCTION

OR

CLEAN

THE

BATTERY

.

Abnormal system noise:

- Piping vibration;

SUPPORT

PIPING

.

- Noisy compressor;

CHECK

AND

CHANGE

IF

NECESSARY

.

- Hissing expansion valve;

CHECK

AND

ADD

REFRIGERANT

IF

NECESSARY

.

- Badly fitting panels;

INSTALL

CORRECTLY

.

Compressor loses oil:

- Leaking refrigeration circuit;

REPAIR

LEAK

.

Water loss:

- Defective entering or leaving connections;

CHECK

AND

TIGHTEN

IF

NECESSARY

.

The unit does not defrost
(only for 30RH units):

- Four-way reversing valve faulty;

CHECK

AND

REPLACE

THE

VALVE

IF

NECESSARY

.

- Defrost sensor broken;

CHECK

AND

REPLACE

THE

SENSOR

IF

NECESSARY

.