IPDU connected to the cascaded KVM to servers connected to the master
KVM/net.

The following error message appears if you try to configure a master KVM
port with the slave connected IPDU.

•

If the KVM port is on the cascaded device, for example Slave-1, the power
outlets can be assigned from the IPDUs connected to the master KVM/net
or from the IPDUs connected to Slave-1.

Perform the following procedure to enable a user who is connected to a server
through a KVM port to perform power management.

Before you start make sure the following prerequisites are complete:

•

The computer is plugged into an IPDU connected to the KVM/net’s
AUXport.

•

The AUXport has been configured for power management.

•

You know the outlet number or numbers to which the computer’s power
cable or cables are plugged.

1. In Expert mode, go to Configuration>KVM>Devices.

The Devices form appears.

2. Select the Device that contains the port(s) to be configured and click the

Port button.

The Port Name list appears.