Crestron Commercial Lighting Design Guide

22

Power Switching

3. Number of Loads

GLPS-___-___-___-___-___-___

Find the row in the table that matches your choices in steps 1 and 2. The numbers in blue represent the maximum number of loads for
each cabinet size. Choose a cabinet size, and do not exceed the maximums when designing the panel. See page 28 for more
information on the cabinet sizes.

Cabinet Size

Medium

Large

Extra Large

Maximum #

of Loads

HSW-MLO

30

32

42

HSW-MCB

27*

32

39*

SW-MLO

30

42

-

SW-MCB

27*

39*

-

*If using 120/208V and 125A MCB, reduce the maximum number of loads shown by three.

4. Voltage

GLPS-___-___-___-___-___-___

To specify the circuit breaker voltage, enter “

120

” for 120/208V or “

277

” for 277/480V.


5. AIC Rating

GLPS-___-___-___-___-___-___

Choose one of the following values from the appropriate column to specify the Ampere Interrupting Capacity of the circuit breakers.

120 Volt

277 Volt

10K 18K
22K 35K
65K 65K











6. Door Option

GLPS-___-___-___-___-___-___

Enter “

ND

” to omit the local control access door. Otherwise truncate this from the model name.
















What is AIC?

When a short circuit occurs, a large amount of current flows into the circuit breaker and it trips. The
Ampere Interrupt Capacity rating is the maximum current the breaker can safely interrupt. If the short
circuit current exceeds the AIC rating of the breaker, the circuit breaker may fail. For safe operation,
the AIC rating must exceed the available fault current at the panel.