Controls, Electrical data, Controls electrical data ,10 – Carrier 50AH User Manual

Page 9

Advertising
background image

9

ELECTRIC HEATER STATIC PRESSURE DROP (in. wg)

NOTE: Above electric heaters are

not UL (Underwriters’ Laboratories) or CSA (Canadian Standards Association)

listed for use with optional high-static evaporator-fan motor (048, 060 units only).

Controls

Operating sequence
Cooling —
Thermostat calls for cooling. Indoor (evapora-
tor) fan relay is energized and starts evaporator fan. Com-
pressor contactor is energized to start compressor and
condenser fan (up to a 5-minute delay on single-phase
units). When room thermostat is satisfied, the evaporator
fan, compressor, and condenser fan shut off.
Continuous fan operation — The thermostat can be
set for continuous operation by setting the fan switch to
ON.

Electrical data

LEGEND

*Optional evaporator-fan motor nameplate data.

ELECTRIC HEATER

UNIT 88EN

UNIT

50AH

MIN

CFM

UNIT CFM

600

800

1000

1200

1400

1600

1800

2000

2200

0500CA01

024, 036

1-stage

heat

400

.02

.04

.06

.10

—

—

—

—

—

0075CA01

510

.03

.06

.10

.16

—

—

—

—

—

0115CA01

620

.04

.08

.13

.19

—

—

—

—

—

0075EA01

320

1150EA01

720

0100EA01

048, 060

2-stage

heat

970

—

—

—

.04

.06

.08

.12

.15

.17

0150EA01

1240

0200EA01

1350

—

—

—

.08

.11

.14

.18

.22

.26

0300EA01

1220

0300CA01

1220

0100FA01

1130

—

—

—

.04

.06

.08

.12

.15

.17

0150FA01

1360

0200FA01

1350

—

—

—

.08

.11

.14

.18

.22

.26

0300FA01

1270

UNIT

50AH

V-PH

(60 Hz)

VOLTAGE RANGE

COMPRESSOR

FAN MOTORS

POWER SUPPLY

Evaporator

Condenser

Min Ckt

Amps

MOCP

Amps

Min

Max

RLA

LRA

Hp

FLA

Hp

FLA

024

230-1

207

254

11.4

56

.17

1.10

.50

3.40

19.0

25

036

230-1

207

254

17.2

96

.50

3.20

.75

6.06

29.5

40

208/230-3

187

254

10.3

77

.50

3.20

.75

3.93

19.9

25

460-3

414

508

5.1

40

.50

1.50

.75

1.97

8.9

15

048

230-1

207

254

24.4

150

.75

4.00

1.0

8.35

42.9

60

208/230-3

187

254

15.5

105

.75

4.00

1.0

3.93

27.3

35

460-3

414

508

7.4

55

.75

2.15

1.0

1.97

13.4

20

048*

208/230-3

187

254

15.5

105

1.5

5.60

1.0

3.93

28.9

35

460-3

414

508

7.4

55

1.5

2.80

1.0

1.97

16.3

20

060

230-1

207

254

28.8

169

.75

4.00

1.5

9.50

49.5

60

208/230-3

187

254

17.3

123

.75

4.00

1.5

4.82

30.4

40

460-3

414

508

9.0

62

.75

2.15

1.5

2.41

15.8

20

060*

208/230-3

187

254

17.3

123

1.5

5.60

1.5

4.82

32.0

40

460-3

414

508

9.0

62

1.5

2.80

1.5

2.41

16.0

20

HACR — Heating, Air Conditioning, and Refrigeration
Hp

— Horsepower

FLA

— Full Load Amps

LRA

— Locked Rotor Amps

MOCP — Maximum Overcurrent Protection (HACR breaker)
RLA

— Rated Load Amps

Advertising