Cable Routing Procedures for the Dell PowerEdge T320 & T420 Systems

4

Introduction

This white paper covers recommended cable routing procedures for the Dell™ PowerEdge™ T320 & T420
systems in the following racks:

• PowerEdge 2410, 4210
• PowerEdge 2420, 4220, 4820 (including wide and deep versions)
• PowerEdge Energy Smart 4020S, 4620S


If you are using the optional cable management arm (CMA), following these procedures will allow you
to extend the system from the rack for service without powering down or disconnecting the cables. If
you are not using the CMA, following these procedures will ensure secure attachment and strain relief
of the cables behind the system.

For guidelines on how to route cables within the rack, refer to the Dell Best Practices Guide for Rack
Enclosure
white paper. For additional details regarding potential interferences between the CMA and
rear-mount power distribution units (PDUs) in Dell racks as well as general information about third
party rack compatibility, refer to the Dell Enterprise Systems Rail Sizing and Rack Compatibility Matrix
located at

http://content.dell.com/us/en/enterprise/d/business~solutions~engineering-

docs~en/Documents~rail-rack-matrix.pdf.aspx

.

Section 1: Cabling a PowerEdge T320 & T420 system with a CMA

This section details how to cable the PowerEdge T320 & T420 systems using a CMA. If you are cabling
the system without the optional CMA, refer to Section 3.

Follow the instructions contained in the Rack Installation Instructions in the rail kit to install the server
into the rack. Once installed, use these instructions to install the cables. All illustrations in the
following sections were created using a PowerEdge T320 system.

NOTE: The PowerEdge T320 & T420 systems are compatible with both the PowerEdge T610 rails and
CMA and the PowerEdge T620 rails and CMA.

1.1. Connecting the cables to the system

Attach the CMA tray to the back of the rails as described in the CMA Installation Instructions provided
in the CMA kit. Connect all applicable cables to the rear of the system and verify that all connections
are secure. See Figure 1.