Dell UPS 1000R User Manual

Page 13

Advertising
background image

Configuring the EMP

7

Temperature and humidity measurements are displayed in a graduated bar (see Figure 6). The red

zones to the left and right of the bar represent the low and high thresholds. If notification is turned on,

an alarm is generated when the measured value enters one of these zones. The cursor indicates the

current reading.

Figure 6. Graduated Bar (Humidity Bar Shown)

3 Click Reset Min/Max to display the time-stamped minimum and maximum since the previous reset

for temperature or humidity.

NOTE:

The EMP is factory-calibrated, but you can apply an offset to adjust the measurement.

4 Click Calibrate for temperature or humidity to open the Offset page.
5 Enter the Offset value and click Apply or Save.

NOTE:

Input #1 and Input #2 display the status of the two contacts acquired by the EMP. The last status change of

each contact is time stamped.
Before the status of the contact closures display, you must configure and enable this feature on the Environment

Settings page.