Configuring the EMP

9

2 Enter changes. Configurable environment settings are:

Parameter

Description

Sensor name

The name given to the EMP. Dell recommends using a name that

identifies the location of the EMP.

Temperature

Choice of the temperature unit (°C or °F) from the list.

High threshold (temperature)

If the temperature exceeds the set threshold, a notification is triggered if

enabled. The default value is 40°C / 104°F.

Low threshold (temperature)

If the temperature falls below the set threshold, a notification is triggered

if enabled. The default value is 5°C / 41°F.

Hysteresis (temperature)

Hysteresis must be set to prevent multiple notifications if temperature

fluctuates around a threshold. The default value is 2°C / -3.6°F.
The high alarm disappears when the value drops below the high threshold

minus hysteresis value.
The low alarm disappears when the value returns above the low threshold

plus the hysteresis value.

High threshold (humidity)

If the humidity exceeds the set threshold, a notification is triggered if

enabled. The default value is 90%.

Low threshold (humidity)

If the humidity falls below the set threshold, a notification is triggered if

enabled. The default value is 5%.

Hysteresis (humidity)

Hysteresis must be set to prevent multiple notifications if humidity

fluctuates around a threshold. The default value is 5%.
The high alarm disappears when the value drops below the high threshold

minus the hysteresis value.
The low alarm disappears when the value returns above the low threshold

plus the hysteresis value.

Input #1 and Input #2

An identifier corresponding to the acquired contact (for example: rack

door, air conditioning, or generator unit). The maximum length is 28

characters.

when closed and when open

The names associated with the two contact positions (for example “open”

and “closed” for a door, “on” and “off” for a generator).