Dell Powervault DL2300 User Manual

Page 8

Advertising
background image

Environmental

Temperature (Continuous Operation)

Temperature Ranges (for altitude less than 950 m or
3117 ft)

10 °C to 35 °C (50 °F to 95 °F) with no direct sunlight on
the equipment

NOTE: For information on supported expanded
operating temperature range and configurations,
see the

Owner's Manual

support.dell.com/manuals.

Humidity Percentage Range

10% to 80% Relative Humidity with 26 °C (78.8 °F)
maximum dew point.

Relative humidity

Storage

5% to 95% RH with 33 °C (91 °F) maximum dew point.
Atmosphere must be non-condensing at all times

Maximum vibration

Operating

0.26 G

rms

at 5 Hz to 350 Hz (all operation orientations).

Storage

1.87 G

rms

at 10 Hz to 500 Hz for 15 min (all six sides

tested).

Maximum shock

Operating

One shock pulse in the positive z axis (one pulse on each
side of the system) of 31 G for 2.6 m in the operational
orientation.

Storage

Six consecutively executed shock pulses in the positive
and negative x, y, and z axes (one pulse on each side of
the system) of 71 G for up to 2 m.

Altitude

Operating

3048 m (10,000 ft).

Storage

12,000 m ( 39,370 ft).

Operating Altitude De-rating

Up to 35 °C (95 °F) maximum temperature is reduced by 1
°C/300 m (1 °F/547 ft) above 950 m (3,117 ft)
35 °C to 40 °C (95 °F to 104 °F) maximum temperature is

reduced by 1 °C/175 m (1 °F/319 ft) above 950 m (3,117 ft)
40 °C to 45 °C (104 °F to 113 °F) maximum temperature is

reduced by 1 °C/125 m (1 °F/228 ft) above 950 m (3,117 ft)

Particulate Contamination

NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and
gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits
specified below and are the reason for the damage and/or failures to your equipment it may be necessary for you
to remediate the environmental conditions that are causing the damage and/or failures. Remediation of
environmental conditions will be the responsibility of the customer.

Air Filtration

Data center air filtration as defined by ISO Class 8 per
ISO 14644-1 with a 95% upper confidence limit.

8

Advertising