Outback Power Systems MATE2 User Manual
Page 104

0
ADV/SETTINGS/WARNING
changes made could
adversely effect
system performance
Before entering the
ADVANCED screens, a
warning message appears.
Any changes can always
be undone, different values
entered, or the MATE can
be returned to its factory
default settings.
After pressing the
<INC> soft key until
the password number
141 appears, the ad-
vanced screens for the
FX. Charge Controller,
and MATE become
available.
The advanced FX screens include:
u
FX search sensitivity, pulse length,
and pulse spacing
u
low battery cut-off and cut-in set
points
u
adjustments to the output voltage
and charger limits
u
absorb, float, refloat, and equalize
settings
u
resetting the FX to factory defaults
u
AC grid usage and limits
u
generator programming
u
AUX functions, including genalert,
loadshed, vent fan, and diversion
functions
u
FX stacking
VAC and VDC calibrations
u
selling voltage and grid tie settings
u
VAC and VDC calibrations
ADV/PASSWORD
enter the password
132
ENTER INC DEC EXIT
ADV-------------------------------------
choose product
FX
C C DC MATE
The advanced CC screens include:
u
AUX output function
u
AUX output control
The advanced MATE screens include:
u
HBX grid use and drop setpoints
and delays, AC input control
u
Griduse weekday and weekend
start and stop times
u
AGS or advanced generator start
functions such as SETUP, QUIET
TIME, VOLT START, LOAD START,
MUST RUN, EXERCISE, and TIM-
ERS
u
resetting the MATE2M to factory
default values
The ADV(anced) menu al-
lows a user to more precise-
ly adjust the inverter and
charger functions as well as
the generator function and
grid-tie setpoints. The ADV
menu is password-protect-
ed requiring the password
141 be entered before ac-
cesssing the screens.
The advanced FLEXnet DC screens include:
u
battery bank capacity
u
enable or disable shunts
u
establish the end of charge amps, end of
charge voltage, and amount of time the charge
parameters must be met
u
AUX functions