Environmental

NOTE: Applies to data center environments only.
Air filtration requirements do not apply to IT
equipment designed to be used outside a data
center, in environments such as an office or factory
floor.

Conductive Dust

NOTE: Applies to data center and non-data center
environments.

Air must be free of conductive dust, zinc whiskers, or
other conductive particles.

Corrosive Dust

NOTE: Applies to data center and non-data center
environments.

Air must be free of corrosive dust.

Residual dust present in the air must have a

deliquescent point less than 60% relative

humidity.

Airborne Contaminant Level

Class

G1 as defined by ISA-S71.04-1985.

Gaseous Contamination

Copper Coupon Corrosion Rate

<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.

Silver Coupon Corrosion Rate

<200 Å/month as defined by AHSRAE TC9.9.