Environmental

NOTE: Outside the standard operating temperature
(10 °C to 35 °C), the system can operate down to 5 °C
or up to 40 °C for a maximum of 10% of its annual
operating hours.

For temperatures between 35 °C and 40 °C, de-rate

maximum allowable dry bulb temperature by 1 °C per 175

m above 950 m (1 °F per 319 ft).

< 1% of annual operating hours

–5 °C to 45 °C at 5% to 90% RH with 26 °C dew point.

NOTE: Outside the standard operating temperature
(10 °C to 35 °C), the system can operate down to –5
°C or up to 45 °C for a maximum of 1% of its annual
operating hours.

For temperatures between 40 °C and 45 °C, de-rate

maximum allowable dry bulb temperature by 1 °C per 125

m above 950 m (1 °F per 228 ft).

Expanded Operating Temperature Restrictions

Do not perform a cold startup below 5 °C.

The operating temperature specified is for a

maximum altitude of 3050 m (10,000 ft).

PCIe SSD is not supported.

GPU is not supported.

130 W (4 core) processor is not supported.

Redundant power supplies are required.

Non Dell qualified peripheral cards and/or

peripheral cards greater than 25 W are not

supported.

NOTE: The following additional restrictions apply to
DL2300.

Maximum 95 W processor supported on 3.5 inch

hard drive chassis.

Only SSDs are allowed in the hard drive slots at

the back of the 3.5 inch hard drive chassis.

Storage Temperature

–40 °C to 65 °C (–40 °F to 149 °F) with a maximum
temperature gradation of 20 °C per hour.