Cabling Instructions for the –48 VDC Power Supply

CAUTION:

Never defeat the ground conductor or operate the equipment in the absence of a suitably installed

ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain
that suitable grounding is available.

Input Requirements

Kit Contents

Tyco 556879-3 connector housing (1) or equivalent

Tyco 556880-2 connector contacts (3) or equivalent

AMP 2-320568-2 ring-tongue terminal (1) or equivalent

#8-32 nut equipped with lock washer (1)

Required Tools

Wire-stripper pliers capable of removing insulation from size 10 AWG solid or stranded, insulated
copper wire

NOTE:

Use alpha wire part #3080 or equivalent (65/30 stranding)

One UL 1015 10 AWG, 2 m maximum (stranded) black wire (–48 VDC)

One UL 1015 10 AWG, 2 m maximum (stranded) red wire (48 VDC return)

One UL 1015 10 AWG, 2 m maximum green, stranded wire (optional connector ground)

One UL 1015 10 AWG, 2 m maximum green/yellow, green with a yellow stripe, stranded wire
(safety ground)

AMP 90871-1 hand-crimping tool or equivalent

Supply voltage:

(48–60) VDC

Current consumption:

20 A maximum