Assembling and connecting the safety ground wire, Connecting the -48 vdc power cable, Connecting the –48 vdc power cable – Dell POWEREDGE 2950 User Manual

Page 8

Advertising
background image

6

Cabling Instructions for the –48 VDC Power Supply

Assembling and Connecting the Safety Ground Wire

1 Strip the insulation from the end of the green/yellow wire, exposing approximately 4.5 mm

(0.175 inches) of copper wire.

2 Using a hand-crimping tool, crimp the ring-tongue terminal to the green/yellow wire.
3 Connect the safety ground to the grounding post on the back of the system using a #8-32 nut

equipped with a locking washer (see Figure 1-2).

Figure 1-2.

Power Supply Safety Ground

Connecting the –48 VDC Power Cable

To connect the

–48 VDC

power cable, plug the

–48 VDC

power cable into the system power supply.

1

green/yellow safety ground

2

grounding post

3

locking washer

4

#8-32 nut

1

2

3

4