Dell UPS 4200R User Manual

Page 24

Advertising
background image

44

|

Operation

Table 6. Settings (continued)

Description

Default Setting

Available Settings

Overload Alarm Level

[10%] [20%] [30%]...[100%]

If 100%, the UPS issues an Output Overload alarm
at load > 100%.

NOTE:

Output Overload Level 1 by default is set to

100% and is configurable from 10% to 100% in 10%
increments through the LCD setting menu. This
allows customers to be alerted before the UPS has
reached its rated capacity limits.

100%

Power Strategy

[Normal] [High Efficiency] [Converter]

See “Setting Power Strategy” on page 48.

High Efficiency

Automatic Start Delay

[Off] [0s] [1s] [2s]...[32767s]

See “Configuring Load Segments” on page 50.

0s

Automatic on Battery Shutdown

[Off] [0s] [1s] [2s]...[32767s]

See “Configuring Load Segments” on page 50.

Off

Start on Battery

[Enabled] [Disabled]

NOTE:

Battery start is disabled from the factory and

remains disabled until the UPS has been powered
from utility and enters Standby mode. After the
UPS has been started once from utility, the Start on
Battery feature is automatically enabled. After this is
set by the user, it remains set.

Enabled

Battery Saving Mode

[Disabled] [10%] [20%] [30%]...[100%]

The UPS output is turned off in five minutes if the
UPS is on battery and output power is below the
selected level.

Disabled

On Battery Notice Delay

[0] [1s] [2s]...[99s]

The UPS issues a “UPS on battery” notice in the
specified number of seconds after the UPS starts to
discharge the batteries.

0s

Site Wiring Fault Alarm

[Enabled] [Disabled]

Enabled for low
voltage models;
Disabled for all other
models

Advertising