Retrieving the event log, Behavior on overload – Dell UPS 4200R User Manual

Page 49

Advertising
background image

69

Troubleshooting

|

Table 15. Typical Alarms and Conditions (continued)

Alarm or Condition

Action

Possible Cause

Battery test did not run or
was interrupted.

One of the conditions listed in
“Running Automatic Battery
Tests” on page 54 was not
present.

Resolve the condition, then restart the test.

The UPS does not transfer to
Bypass mode.

The bypass utility does not
qualify.

Check the bypass utility. The UPS is receiving
bypass utility power that may be unstable or in
brownout conditions.

Bypass mode is disabled.

Check that the Bypass settings are configured
correctly. See “Settings” on page 43.

UPS on Bypass

(Notice 169)

Continuous Alarm

The UPS is operating from
Bypass mode.

The equipment transferred to bypass utility
power. Battery mode is not available and your
equipment is not protected; however, the
utility power continues to be passively filtered
by the UPS. Check for one of the following
alarms: overtemperature, overload, or UPS
failure.

On Manual Bypass

(Notice 143)

Intermittent Alarm

UPS was manually commanded
to transfer to Bypass mode and
will remain in bypass until
commanded.

None.

UPS on Battery

(Notice 168)

Intermittent Alarm

A utility failure has occurred
and the UPS is in Battery mode.

The UPS is powering the equipment with
battery power. Prepare your equipment for
shutdown.

Battery Disconnected

(Alarm 199)

Continuous Alarm

The UPS does not recognize
the internal batteries.

If the condition persists, contact your service
representative.

Battery voltage is lower than the
batteries disconnected level
defined for this UPS. This may
be due to a blown fuse,
intermittent battery
connection, or battery cable
being disconnected.

Verify that all batteries are properly
connected. If the condition persists, contact
your service representative.

Low Battery Warning

(Alarm 56)

Continuous Alarm

Battery time remaining or
battery capacity is lower than
the battery low warning level
defined for this UPS.

This warning is approximate. The actual time to
shutdown may vary depending on the UPS load
and presence of an External Battery Module
(EBM).