VENT TERMINAL CLEARANCES

Page 4

REFERENCE LETTER TO

DRAWING

CANADIAN

INSTALLATIONS¹

U.S. INSTALLATIONS²

A = Clearance above grade,
veranda, porch, deck, or

balcony

12 Inches (30 cm)

12 Inches (30 cm)

B = Clearance to window or door
that may be opened

12 Inches (30 cm)

9 Inches (23 cm)

C = Clearance to permanently
closed window

12 Inches (30 cm)

9 Inches (23 cm)

D = Vertical clearance to

ventilated soffit located above
the terminal within a horizontal

distance of 2 Feet (61 cm) from
the center line of the terminal

18 Inches (46 cm)

18 Inches (46 cm)

E = Clearance to unventilated
soffit

18 Inches (46 cm)

18 Inches (46 cm)

F = Clearance to outside corner

12 Inches (30 cm)

12 Inches (30 cm)

G = Clearance to inside corner

12 Inches (30 cm)

12 Inches (30 cm)

H = Clearance to each side of
center line extended above

meter/ regulator assembly

3 Feet (91 cm) within a height
15 Feet (4.5m) above the

meter/regulator assembly

Clearances are in accordance
with local installation codes and

the requirements of the gas
supplier

I = Clearance to service regulator
vent outlet

3 Feet (91 cm)

Clearances are in accordance
with local installation codes and

the requirements of the gas
supplier

J = Clearance to nonmechanical

air supply inlet to building or the
combustion air inlet to any other

appliance

12 Inches (30 cm)

12 Inches (30 cm)

K = Clearance to a mechanical

air supply inlet

6 Feet (1.83 m)

3 Feet (91 cm) above if within

10 Feet (3 m) horizontally

L = Clearance above paved
sidewalk or paved driveway

located on public property

7 Feet (2.13m) A vent shall
not terminate directly above

a sidewalk or paved driveway
that is located between two
single family dwellings and

serves both dwellings.

Clearances are in accordance
with local installation codes and

the requirements of the gas
supplier.

M = Clearance under veranda,
porch, deck, or balcony

12 Inches (30 cm) permitted
only if veranda, porch, deck,

or balcony is fully open on a
minimum of two sides.

Clearances are in accordance
with local installation codes and

the requirements of the gas
supplier.

¹ In accordance with the current CSA-B149.1 Natural Gas and Propane Installation Code
² In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code

Vent Terminal

Air Supply Inlet

Area where terminal is not permitted

FIGURE 1