Anchoring the head, Step 3) anchoring the head, Includes offset and center-set glazing) – EFCO 433 Series User Manual
Page 64: Series 433 triple set installation instructions

June 2012
PART NO. Y017
Page 64 of 90
Series 433 Triple Set Installation Instructions
SECTION VIII: Installation
(Includes Offset and Center-Set Glazing)
Step 3) Anchoring the Head
For D.L.O.s 36" and narrower, the anchors must be spaced 6" from the jamb or
vertical members. For D.L.O.s 36" and wider, the outside anchors must be spaced 6"
from the jamb with the center anchor centered on the D.L.O. See Figure 38 below.
4G29
3G46
1 3/16"
REF.
2 11/16" REF.
6"
"VARIES"
FD
6"
FD
GREATER THAN 36"
FD
EQUAL
FD
EQUAL
6"
6"
FD
8372
8366
8363 SHOWN
8393 SIMILAR
1 1/8"
REF.
3 5/16" REF.
2 11/16" REF.
[FIG. 38]
LESS THAN OR EQUAL 36"
These recommendations are for general erection procedures only. For actual
job conditions, see the details on the shop drawings. For perimeter anchor
type and spacing, refer to the approved shop drawings or consult the project
design professional.