Installation and Application
13
4.0 Installation and Application
Before connecting any components, follow the
safety information in the ETS-Lindgren
Product Information Bulletin included with your
shipment.
The Model 3625/2 is provided with resistors to
help bleed off high voltage transients, but it is
advisable to connect the input and output
connectors to their proper power lines and
loads before connecting the monitor port to the
measurement instrumentation; otherwise,
power surges or transients can damage the test
instrumentation mixers or attenuators.
The Model 3625/2 Line Impedance Stabilization Network (LISN) is nominally
designed for a 25-ampere maximum load capacity, though this rating may be
increased to 30 amperes provided that the duty cycle is reduced to 20%.
Maximum line-to-line voltage must not exceed the 440 volts AC RMS.
Maximum line-to-ground voltage must not exceed 220 volts AC RMS.
Connecting to Power
The safety ground should be connected first
and disconnected last on the input side of the
unit.
The line side of the Model 3626/2 should be connected to the power source
using the three plug sockets provided. Attach these plugs to the pin receptacles
located on the back panel.
When the power is to be disconnected, remove the power source.