Vermont Castings, Majestic Products RHE Natural Vent Insert

During any pressure testing of the gas line system,
when the test pressures are to exceed 1/2 psi (3.5 kpa)
the fireplace and its gas valve must not be connected
to that system.

At test pressures equal to or less than 1/2 psi, the gas
valve of the fireplace may be connected to the gas line,
but must be in the closed position.

Some municipalities have additional local codes, it is
always best to consult the local authority and the CSA-
B149.1 installation code in Canada.

FOR U.S.A Installations consult the current National
Fuel Gas Code, ANSI Z223.1

Always check for gas leaks with a mild soap
and water solution. Do not use an open
flame for leak testing.

1/2" Gas Supply

1/2" x 3/8" Reducer

3/8" x 3/8" Shut Off
Valve

3/8" Union

3/8" Nipple

FP1278

Fig. 4 Typical gas supply installation.

it

HI

LO

OFF

PILOT

Thermostat
Bulb

Brass
Plug

Gas Inlet

Thermocouple Inlet

Pilot Tube Entry

Manifold Gas
Outlet

Brass Plug

Pressure
Regulator

Control Knob

Control Knob

Pilot
Adjustment
Screw

Minimum Rate Screw
(Nonadjustable)

HV118

Fig. 5 On fireplaces equipped with the Eurosit 630 gas
valves, there are brass plugs in two of the holes. These
plugs are not to be removed. The gas inlet hole has a plastic
cap in it. Remove the plastic cap and connect your gas
supply line at this point.

The MN/MP valve control used on the
RHE25 does not include the thermostat
bullb as shown in Figure 5.

Installation of Remote Switch

for RN/RP Gas Valves

1. Thread wire through gas inlet opening on the right

side of fireplace. Do not cut wire or insulation on
metal edges.

2. Slide switch assembly from the back, between

subframe and trim, then fasten the screw. (Fig. 6)

3. For left side installation reverse switch position in

bracket and repeat Step 2. (Fig. 7)

4. Connect wiring to gas valve (Fig. 8a & b) and switch.

Right Side Installation

Left Side Installation

Trim Right
Side

Trim Top

Trim Left
Side

ON/OFF Switch
Assembly

Trim
Screw

Wiring from
Millivolt Gas
Valve

Trim
Screw

ON/OFF Switch Assembly

FP1253

Fig. 6 Slide switch assembly between subframe and trim.

Bracket Switch

ON/OFF
Switch

FP1254

Fig. 7 For left side installation, reverse switch position in
bracket.

PILO

T

THTP

TP

TH

Valve

Thermopile

FP382a

Fig. 8a ON/OFF switch or millivolt thermostat.